Air Velocity Transmitter Series 641
To inquire, Select Product/s & Click on

Product Code : 15

[Select]
Product Specification
Air Velocity Transmitter Series 641
The new Series 641 Air Velocity Transmitter is the ideal instrument for monitoring air flow. This transmitter uses a heated mass flow sensor which allows for precise velocity measurements at various flow rates and temperatures. The 641’s 16 field selectable ranges provides it the versatility to be selected for several air flow applications. The optional LED produces a complete, low-cost solution for local indication of air flow.

Features
  • Ranges to 15,000 FPM or 75 MPS
  • Optional Bright LED Display
  • Easy Push Button Set-up
  • Compact Housing
  • 4-20 mA Output
  • Digital Filter for Signal Damping
Application
  • Exhaust Stack Flow Monitoring
  • Air Control in Drying Processes
  • HVAC Air Velocity Measurements
  • Fan Supply and Exhaust Tracking
  • Clean Room Fresh Air Supply
  • Ensure Proper Lab Hood Exhaust Flow Rates
Model Number
Probe Length*
641-6
641-6-LED
641-12
641-12-LED
641-18
641-18-LED
641-24
641-24-LED
641-30
641-30-LED
641-36
641-36-LED
6˝ (152.4 mm)
6˝ (152.4 mm)
12˝ (304.8 mm)
12˝ (304.8 mm)
18˝ (457.2 mm)
18˝ (457.2 mm)
24˝ (609.6 mm)
24˝ (609.6 mm)
30˝ (762 mm)
30˝ (762 mm)
36˝ (914 mm)
36˝ (914 mm)
*Other probe lengths available contact factory.

Specification
  • Service: Clean air and compatible, non-combustible gases.
  • Accuracy:
  • 3% FS Process gas: 32 to 122°F (0 to 50°C).
  • 4% FS Process gas: -40 to 32°F & 122 to 212°F
  • (-40 to 0°C & 50 to 100°C).
  • Response Time: Flow: 1.5 seconds to 95% of final value (output filter set to minimum).
  • Temperature Limits: Process: -40 to 212°F (-40 to 100°C). Ambient: 32 to 140°F (0 to 60°C).
  • Pressure Limit: 100 psi (6.89 bar) maximum.
  • Humidity Limit: Non-Condensing.
  • Power Requirements: 12–35 VDC, 10–16 VAC. 1.5 A rating required on supply due to initial power surge drawn by transmitter.
  • Output Signal: 4-20 mA, isolated 24V source, 3 or 4-wire connection.
  • Output Filter: Selectable 0.5 –15 (seconds).
  • Loop Resistance: 600 ohms max.
  • Current Consumption: 300 mA max.
  • Electrical Connections: Screw terminal.
  • Process Connections: 1/2" male NPT.
  • Enclosure Rating: Designed to meet NEMA 4X (IP66) for non LED models only.
  • Mounting Orientation: Unit not position sensitive. Probe must be aligned with airflow.
  • Weight: 12.6 oz (357.2 g).
  • Agency Approvals: CE.

Optional Display Version

  • Display: 4-1/2 digit 1/2" red LED.
  • Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and 15,000 FPM ranges).
  • Weight: 13.3 oz (377 g).
Accessories
  • A-156 - Flange mounting plate with 1/2" female NPT.
  • A-158 - Split flange.
  • A-159 - Mounting gland with 1/2" male NPT.
Other Products in 'Air Velocity' category
Pocket Wind Meter Series MW
Pocket Wind Meter Series MW
 
<< Back
 
 
  Contact Details
A L M ENGINEERING & INSTRUMENTATION PVT. LTD.
304, Damji Shamji Industrial Complex, L.B.S. Marg, Kurla (W), Mumbai - 400070, Maharashtra, India
Phone:91-22-25126700/25126900/25126500/42211000/25123020
Fax:91-22-25126700/25123020
Send Mail   Send SMS   
Contact Now
Key Personnel
Mr. Sarfraz Panjwani (Managing Director)
Mobile:+919820106157, +919833140352



Translate In : View in English View in Spanish View in French View in German View in Italian View in Chinese (Simplified) View in Japanese View in Korean View in Arabic View in Portuguese
Copyright © 2009 by ALM ENGINEERING & INSRUMENTATION PVT. LTD. All Rights Reserved.